Control Of Electronic Expansion Valve - Daikin VRV Aurora RXLQ-TATJU Series Service Manual

Table of Contents

Advertisement

SiUS341802EC
9.6

Control of Electronic Expansion Valve

Electronic expansion valves in indoor units have the functions of conducting superheating degree
control in cooling operation and subcooling degree control in heating operation. However, if the
indoor units receive any control command such as a protection control command or a special
control command from the outdoor unit, the units will give a priority to the control command.
 Superheating degree control in cooling operation
This function is used to adjust the opening of the electronic expansion valve so that superheating
degree (SH), which is calculated from the detection temperature (Tg) of the gas pipe thermistor
(R3T) and the detection temperature (Tl) of the liquid temperature thermistor (R2T) of the indoor
unit, will come close to a target superheating degree (SHS).
At that time, correction to the superheating degree is made according to the differences (T)
between set temperature and suction air temperature.
SH = Tg – Tl
Where,
SH: Evaporator outlet superheating degree
Tg: Indoor unit gas pipe temperature (R3T)
Tl: Indoor unit liquid pipe temperature (R2T)
SHS: Target superheating degree
SHS (Target SH value)
 Normally 5°C (9°F).
 As T (Remote controller set temp. – Suction air temp.) becomes larger, SHS becomes lower.
 As T (Remote controller set temp. – Suction air temp.) becomes smaller, SHS becomes
 Subcooling degree control in heating operation
This function is used to adjust the opening of the electronic expansion valve so that the high
pressure equivalent saturated temperature (Tc), which is converted from the detected pressure of
the high pressure sensor in the outdoor unit, and the subcooling degree (SC), which is calculated
from the detected temperature (Tl) of the liquid temperature thermistor (R2T) in the indoor unit, will
come close to the target subcooling degree (SCS).
At that time, corrections to the subcooling degree are made according to differences (T) between
set temperature and suction air temperatures.
SC = Tc – Tl
Where,
SC: Condenser outlet subcooling degree
Tc: High pressure equivalent saturated temperature detected by the high pressure sensor (S1NPH)
Tl: Indoor unit liquid pipe temperature (R2T)
SCS: Target subcooling degree
SCS (Target SC value)
 Normally 5°C (9°F).
 As T (Remote controller set temp. – Suction air temp.) becomes larger, SCS becomes lower.
 As T (Remote controller set temp. – Suction air temp.) becomes smaller, SCS becomes
Part 4 Functions and Control
higher.
higher.
Outline of Control (Indoor Unit)
122

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv aurora rxlq-tatja seriesVrv aurora rxlq-tbtja seriesVrv aurora rxlq-taycu seriesVrv aurora rxlq-tayca seriesVrv aurora rxlq-tbyca seriesVrv aurora rxlq-taydu series ... Show all

Table of Contents