Daikin VRV Aurora RXLQ-TATJU Series Service Manual page 166

Table of Contents

Advertisement

Field Settings for Indoor Unit
1.4.18 Airflow Setting when Heating Thermostat is OFF
This setting is used to set airflow when heating thermostat is OFF.
If the airflow setting when thermostat is OFF is set to 03: OFF, the air in the indoor unit will be
stagnant and suction air thermistor may not detect room temperature correctly, resulting in
problems that thermostat will not be ON easily.
Use optional remote sensor in such conditions, or set the field setting 10 (20)-2 to 03 (only remote
controller thermistor).
 When thermostat OFF airflow volume up mode is used, careful consideration is required before
deciding installation location.
1.4.19 Automatic Mode Differential
This setting makes it possible to change differential values for mode selection while in automatic
operation mode, only when the wireless remote controller or any central remote controller is
connected.
The automatic operation mode setting is made by the use of the operation mode selector button.
1.4.20 Auto Restart after Power Failure
Mode
12 (22)
When the Auto Restart after Power Failure setting is turned OFF, all the units will remain OFF after
power failure, or after the main power supply is restored. When this setting is turned ON (factory
setting), the units that were operating before the power failure will automatically restart operation
after power failure, or after the main power supply is restored.
Due to the aforementioned, when the Auto Restart after Power Failure setting is ON, be careful for
the following situations that may occur.
1. The air conditioner will start operation suddenly after power failure,
Caution
2. During maintenance, if the main power supply is turned OFF while the
159
Mode No.
First Code No.
12 (22)
First Code
Mode No.
No.
01
12 (22)
4
(0°F)
First
Second
No.
Code No.
Code No.
01
5
02
or when the main power supply is restored. The user might be surprised
and wonder why the air conditioner turned ON suddenly.
units are in operation, the units will automatically start operation
(the fan will rotate) after the power supply is restored due to completion
of the maintenance work.
Second Code No.
01
3
02
03
02
03
0°C
1°C
2°C
(1.8°F)
(3.6°F)
Contents
LL tap
Set fan speed
OFF
Second Code No.
04
05
06
3°C
4°C
5°C
(5.4°F)
(7.2°F)
(9.0°F)
Contents
OFF
ON
Part 5 Field Settings and Test Operation
SiUS341802EC
: Factory setting
: Factory setting
07
08
6°C
7°C
(10.8°F)
(12.6°F)
: Factory setting

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv aurora rxlq-tatja seriesVrv aurora rxlq-tbtja seriesVrv aurora rxlq-taycu seriesVrv aurora rxlq-tayca seriesVrv aurora rxlq-tbyca seriesVrv aurora rxlq-taydu series ... Show all

Table of Contents