SiUS341802EC
(1) Microcomputer normal monitor
This monitor blinks while in normal control, and turns ON or OFF when an error occurs.
(2) Segment display
Used to check the transmission and display the transmission state between indoor and outdoor
units, the contents of error, and the contents of field setting.
(3) BS button
Used to change mode.
(4) DIP switch
Used to make field settings.
The figure below shows the required position of the DIP switches on spare PCB. Change DIP
switches at time of power disconnected.
Application model
RXLQ72TA
RXLQ72TB
RXYQ72TA
RXLQ96TA
RXLQ96TB
RXYQ96TA
RXLQ120TA
RXLQ120TB
RXYQ120TA
RXYQ144TA
RXYQ168TA
Part 5 Field Settings and Test Operation
The setting method ( represents the position of switches)
ON
OFF
1 2 3 4
1 2 3 4
DS1
DS2
ON
OFF
1 2 3 4
1 2 3 4
DS1
DS2
ON
OFF
1 2 3 4
1 2 3 4
DS1
DS2
ON
OFF
1 2 3 4
1 2 3 4
DS1
DS2
ON
OFF
1 2 3 4
1 2 3 4
DS1
DS2
Field Setting from Outdoor Unit
Set DS2-2 to ON.
Set DS2-1 and DS2-2 to ON.
Set DS2-3 to ON.
Set DS2-2 and DS2-3 to ON.
Set DS2-1, DS2-2 and DS2-3 to ON.
174