Field Settings for Indoor Unit
First
Mode
Code
Setting Contents
No.
No.
(Note 2)
Ceiling height setting, Setting
0
of normal airflow
Airflow direction setting
1
Swing pattern settings
2
13 (23)
Airflow direction adjustment
4
range
Setting of static pressure
5
selection
External static pressure
6
settings
Optional kit setting (UV lamp
4
+ humidifier + economizer)
Dry mode set temperature
5
14 (24)
Mold proof operation setting
9
11
Gas furnace test mode
0
Drain pump operation setting
Humidification when heating
1
thermostat is OFF
15 (25)
2
Direct duct connection
Drain pump and humidifier
3
interlock selection
5
Individual ventilation setting
Display of error codes on the
1b
4
remote controller
0
Room temperature display
Thermistor sensor for auto
changeover and setback
1
1c
control by the remote
controller
Access permission level
3
setting
2
Setback availability
1e
Setting restricted/permitted
14
for airflow block
Note(s)
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they
3. Do not make settings other than those described above. Nothing is displayed for functions the
4. 88 or Checking the connection. Please stand by. may be displayed to indicate the remote
145
01
Standard
4-direction
airflow
All direction
synchronized
swing
Draft prevention
Room
temperature
—
OFF
Not equipped
Not equipped
Not
interlocked
Normal
—
Not displayed
Utilize the return
air thermistor
Level 2
N/A
inside parentheses, you can also set by each individual unit. Setting changes however cannot
be checked except in the individual mode for those in parentheses.
cannot be set individually. Setting changes also cannot be checked.
indoor unit is not equipped with.
controller is resetting when returning to the normal mode.
Second Code No.
02
03
High ceiling 1
High ceiling 2
2-direction
3-direction airflow
airflow
Facing
—
swing
Ceiling soiling
Standard
prevention
Refer to page on the right for details.
Refer to page on the right for details.
Refer to page on the right for details.
Same as cooling
mode set
temperature
For high
Standard
humidity areas
Low heat
High heat
Refer to page on the right for details.
Equipped
Equipped
Interlocked
Individual
Two-digit display
Displayed
Utilize the
remote
controller
thermistor
Level 3
Heat only
Cool only
Refer to page on the right for details.
Part 5 Field Settings and Test Operation
SiUS341802EC
Reference
04
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Four-digit
—
display
—
—
—
—
—
—
Cool/heat
Page
160
161
162
162
162
163
165
165
165
165
166
166
166
166
167
167
167
167
168
168
168