Field Settings for Indoor Unit
1.1.4 Simplified Remote Controller
1. Remove the upper part of remote controller.
2. When in the normal mode, press the BS6 button (2) (field setting) to enter the field setting
3. Select the desired MODE No. with the BS2 button (3) (temperature setting ) and the BS3
4. During group control, when setting by each indoor unit (mode No. 20, 22, and 23 have been
5. Press the BS9 button (5) (set A) and select first code No.
6. Press the BS10 button (6) (set B) and select second code No.
7. Press the BS7 button (7) (set/cancel) once and the present settings are confirmed.
8. Press the BS6 button (8) (field setting) to return to the normal mode.
143
Mode No.
Unit No.
(3)
(3)
(2)(8) (7)
mode.
button (3) (temperature setting ).
selected), press the BS8 (4) button (unit No.) and select the indoor unit No. to be set. (This
operation is unnecessary when setting by group.)
First code
No.
Second
code No.
(4)
(5)
(6)
Part 5 Field Settings and Test Operation
SiUS341802EC