SiUS341802EC
[2-60]:
[2-62]:
Adjust cooling and heating system operation to achieve stable capacity.
Note(s)
This setting may result in a longer reaction time to large load variations.
[2-78]:
[2-79]:
Part 5 Field Settings and Test Operation
Gas furnace setting
Default value: 0.
When a gas furnace is connected, the setting [2-60] has to be changed to 1.
Cooling and heating capacity learning control
Default value: 0.
Value
[2-62]
0 (default)
1
2
3
Heat pump lockout temperature
Heat pump is locked out when the outdoor ambient temperature is smaller than the
heat pump lockout temperature.
This is only effective when the heat pump lockout 2 setting [2-37] is Mode 3 to 6.
Value
Heat pump lockout temperature
[2-78]
0 (default)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Heat pump lockout release differential
Heat pump is resumed when the outdoor ambient temperature is recovered by
differential above the heat pump lockout temperature.
Value
Heat pump lockout release differential
[2-79]
0
1 (default)
2
Description
OFF
Cooling adjustment
Heating adjustment
Cooling and heating adjustment
–26.1°C (–15°F)
–23.3°C (–10°F)
–20.5°C (–5°F)
–17.7°C (0°F)
–15°C (5°F)
–12.2°C (10°F)
–9.4°C (15°F)
–6.6°C (20°F)
–3.8°C (25°F)
–1.1°C (30°F)
1.6°C (35°F)
4.4°C (40°F)
7.2°C (45°F)
10°C (50°F)
Forced heat pump lockout
2.8°C (5°F)
5.6°C (10°F)
8.3°C (15°F)
Field Setting from Outdoor Unit
192