Daikin VRV Aurora RXLQ-TATJU Series Service Manual page 227

Table of Contents

Advertisement

SiUS341802EC
Error code
E7 - 01
Fan motor M1F lock (Master)
E7 - 02
Fan motor M2F lock (Master)
E7 - 05
Fan motor M1F momentary overcurrent (Master)
E7 - 06
Fan motor M2F momentary overcurrent (Master)
E7 - 09
Fan motor M1F IPM error (Master)
E7 - 10
Fan motor M2F IPM error (Master)
E7 - 13
Fan motor M1F lock (Slave 1)
E7 - 14
Fan motor M2F lock (Slave 1)
E7 - 17
Fan motor M1F momentary overcurrent (Slave 1)
E7 - 18
Fan motor M2F momentary overcurrent (Slave 1)
E7 - 21
Fan motor M1F IPM error (Slave 1)
E7 - 22
Fan motor M2F IPM error (Slave 1)
E7 - 25
Fan motor M1F lock (Slave 2)
E7 - 26
Fan motor M2F lock (Slave 2)
E7 - 29
Fan motor M1F momentary overcurrent (Slave 2)
E7 - 30
Fan motor M2F momentary overcurrent (Slave 2)
E7 - 33
Fan motor M1F IPM error (Slave 2)
E7 - 34
Fan motor M2F IPM error (Slave 2)
E9 - 01
Electronic expansion valve coil (Y1E) error (Master)
E9 - 03
Electronic expansion valve coil (Y2E) error (Master)
E9 - 04
Electronic expansion valve coil (Y3E) error (Master)
E9 - 05
Electronic expansion valve coil (Y1E) error (Slave 1)
E9 - 06
Electronic expansion valve coil (Y2E) error (Slave 1)
E9 - 07
Electronic expansion valve coil (Y3E) error (Slave 1)
E9 - 08
Electronic expansion valve coil (Y1E) error (Slave 2)
E9 - 09
Electronic expansion valve coil (Y2E) error (Slave 2)
E9 - 10
Electronic expansion valve coil (Y3E) error (Slave 2)
E9 - 20
Defective electronic expansion valve coil (Y1E) (Master)
E9 - 21
Defective electronic expansion valve coil (Y1E) (Slave 1)
E9 - 22
Defective electronic expansion valve coil (Y1E) (Slave 2)
E9 - 23
Defective electronic expansion valve coil (Y2E) (Master)
E9 - 24
Defective electronic expansion valve coil (Y2E) (Slave 1)
E9 - 25
Defective electronic expansion valve coil (Y2E) (Slave 2)
E9 - 26
Electronic expansion valve coil (Y4E) error (Master)
E9 - 27
Electronic expansion valve coil (Y4E) error (Slave 1)
E9 - 28
Electronic expansion valve coil (Y4E) error (Slave 2)
E9 - 29
Electronic expansion valve coil (Y5E) error (Master)
E9 - 31
Electronic expansion valve coil (Y6E) error (Master)
E9 - 32
Electronic expansion valve coil (Y7E) error (Master)
E9 - 34
Electronic expansion valve coil (Y5E) error (Slave 1)
E9 - 36
Electronic expansion valve coil (Y6E) error (Slave 1)
E9 - 37
Electronic expansion valve coil (Y7E) error (Slave 1)
E9 - 39
Electronic expansion valve coil (Y5E) error (Slave 2)
E9 - 41
Electronic expansion valve coil (Y6E) error (Slave 2)
E9 - 42
Electronic expansion valve coil (Y7E) error (Slave 2)
E9 - 44
Defective electronic expansion valve coil (Y3E) (Master)
E9 - 45
Defective electronic expansion valve coil (Y3E) (Slave 1)
E9 - 46
Defective electronic expansion valve coil (Y3E) (Slave 2)
Part 6 Service Diagnosis
Error Description
Troubleshooting
Make a diagnosis of the fan motor of the relevant unit
based on the following.
Fan motor lock: 01, 02, 13, 14, 25, 26
Momentary overcurrent: 05, 06, 17, 18, 29, 30
IPM error: 09, 10, 21, 22, 33, 34
Refer to the E9 flowchart and make a diagnosis of the
relevant electronic expansion valve of the relevant unit
based on the Error code shown to the left.
Troubleshooting by Error Code
Diagnosis
220

Hide quick links: