Protection Control
Heating
Pc
>
3.31 MPa
(480 psi)
9-step down
After 10
Pc
>
seconds
Current step
maintained
Pc
<
3.22 MPa
After 15
(467 psi)
seconds
3-step up
Pc
>
High pressure standby
(2 times within 40 minutes)
99
Normal control
Pc
>
3.39 MPa
(492 psi)
3.31 MPa
(480 psi)
3.72 MPa
(540 psi)
Pc
<
3.17 MPa
(460 psi)
All units
Compressor step: 1
After 10
seconds
High pressure switch (4.0 MPa
(580 psi)
) is activated
Abnormal stop
(E3 is displayed)
SiUS341802EC
Pc: High pressure sensor
detection value for master
unit
Part 4 Functions and Control