Daikin VRV Aurora RXLQ-TATJU Series Service Manual page 388

Table of Contents

Advertisement

Check
Thermistor temperature
(°C)
(°F)
–30
–22
–25
–13
–20
–4
–15
5
–10
14
–5
23
0
32
5
41
10
50
15
59
20
68
25
77
30
86
35
95
40
104
45
113
50
122
55
131
60
140
65
149
70
158
75
167
80
176
85
185
90
194
95
203
100
212
105
221
Drawing No.
381
Type A
Type B
363.8
266.8
197.8
148.2
112.0
85.52
65.84
51.05
39.91
31.44
24.95
19.94
16.04
12.99
10.58
8.669
7.143
5.918
4.928
4.123
3.467
3SA48002
3SA48004
3SA48018
3SA48001
3SA48019
(AD210486)
(AD94A045)
3SA48013
(AD100026)
Resistance (k)
Type C
111.1
111.8
84.95
85.42
65.53
65.80
50.95
51.07
39.92
39.97
31.50
31.51
25.02
25.02
20.00
20.00
16.10
16.10
13.04
13.04
10.63
10.63
8.720
8.711
7.189
7.179
3SA48016
(AD100008)
3S480014
(AD150384)
This data is for reference purposes only.
SiUS341802EC
Type D
336.7
253.1
191.2
144.1
109.6
84.05
64.99
50.64
39.74
31.41
24.98
20.00
16.12
13.07
10.67
8.757
7.227
5.997
5.001
4.191
3.528
2.984
2.534
2.161
1.850
1.590
1.371
1.188
4P159172
(AD010555)
Part 6 Service Diagnosis