Note(s)
The control is automatically switched to the one performed only by the suction air thermistor for
indoor unit when the Second code No. is 01 during group control.
To use the remote controller thermistor control during group control, select the Second code
No. 02 in First code No. 6.
Mode
10 (20)
Note(s)
When the 10 (20)-6 setting is changed to 02, several indoor units are controlled by one remote
controller thermistor, so note that the room temperature might be uneven.
1.4.3 Filter Cleaning Sign
Whether or not to display the sign after operation of a certain duration can be selected.
Mode
10 (20)
Filter cleaning sign is not displayed when a self-cleaning decoration panel is mounted.
1.4.4 Information for intelligent Touch Manager/intelligent Touch Controller
Mode
10 (20)
 When field setting 10 (20)-6-02 is set at the same time as 10 (20)-2-01,02,03, field setting 10
(20)-2 has priority.
When field setting 10 (20)-6-01 is set at the same time as 10 (20)-2-01,02,03, field setting 10 (20)-6
has priority for group connection, and 10 (20)-2 has priority for individual connection.
1.4.5 Time for Absence Area Detection (For units with an infrared presence
sensor only)
By selecting the energy-saving operation mode in the absence, the target temperature is shifted to
the energy-saving end by 1°C (1.8°F) (maximum 2°C (3.6°F)) after the state of absence continues
for a certain period of time. Absent time defined for detection can be selected as follows:
Mode
10 (20)
Part 5 Field Settings and Test Operation
First Code
Second Code
No.
No.
01
6
First Code No. Second Code
No.
01
3
First Code No. Second Code
No.
01
5
Second Code
First Code No.
No.
01
7
No.
Remote controller thermistor control is not permitted during
group control
Remote controller thermistor control is permitted during group
02
control.
No.
02
No.
Only indoor unit sensor value (or remote controller sensor
02
Sensor values according to 10 (20)-2 and 10 (20)-6.
No.
02
Field Settings for Indoor Unit
: Factory setting
Contents
: Factory setting
Contents
Displayed
Not displayed
: Factory setting
Contents
value, if installed.)
: Factory setting
Contents
30 minutes
60 minutes