Daikin VRV Aurora RXLQ-TATJU Series Service Manual page 247

Table of Contents

Advertisement

SiUS341802EC
3.7.3 Indoor Fan Motor Abnormality (FXSQ54TA, FXSQ54TB, FXMQ15-54PB,
FXMQ30-54TB, FXMQ-TA Models)
Applicable
FXSQ54TA, FXSQ54TB, FXMQ15-54PB, FXMQ30-54TB, FXMQ-TA
Models
A6
Error Code
Method of Error
 Error from the current flow on the fan PCB
Detection
 Error from the rotation speed of the fan motor in operation
 Error from the position signal of the fan motor
 Error from the current flow on the fan PCB when the fan motor starting operation
Error Decision
 An overcurrent flows.
Conditions
 The rotation speed is less than a certain level for 6 seconds.
 A position error in the fan rotor continues for 5 seconds or more.
Supposed
 Clogging of a foreign matter
Causes
 Disconnection of the fan motor connectors (X1A and X2A)
 Disconnection of the connectors between the indoor unit control PCB (A1P) and fan PCB (A2P)
 Defective fan PCB (A2P)
 Defective fan motor
Part 6 Service Diagnosis
Troubleshooting by Error Code
240

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv aurora rxlq-tatja seriesVrv aurora rxlq-tbtja seriesVrv aurora rxlq-taycu seriesVrv aurora rxlq-tayca seriesVrv aurora rxlq-tbyca seriesVrv aurora rxlq-taydu series ... Show all

Table of Contents