SiUS341802EC
Automatic lockout
When this setting is made, the auto-backup function will automatically be activated. This will allow
the auxiliary or secondary heat source to be automatically energized in the event of a system failure
related to outdoor units.
Error codes capable of auto-backup are listed in the table below. Please be aware that the error
codes that are not listed do not auto-backup in order to protect the unit.
Error code
(Auto backup
possible)
Part 5 Field Settings and Test Operation
Error contents
A3
Drain level control system abnormality
E3
Actuation of high pressure switch
E4
Actuation of low pressure sensor
E5
Compressor motor lock
E6
Compressor damage alarm
E7
Outdoor fan motor abnormality
E9
Electronic expansion valve coil abnormality
F3
Discharge pipe temperature abnormality
F4
Wet alarm
H3
Harness abnormality (between outdoor unit main PCB and inverter PCB)
H7
Outdoor fan PCB abnormality
H9
Outdoor air thermistor (R1T) abnormality
Discharge pipe thermistor (R21T) abnormality
J3
Compressor body thermistor (R14T) abnormality
Compressor suction thermistor (R12T) abnormality
J5
Suction pipe thermistor (R10T) abnormality
Heat exchanger deicer thermistor (R11T) abnormality
J6
Heat exchanger gas pipe thermistor (R8T, R9T) abnormality
Receiver inlet thermistor (R3T) abnormality
J7
Subcooling heat exchanger liquid pipe thermistor (R7T) abnormality
Subcooling injection thermistor (R16T) abnormality
Heat exchanger liquid pipe thermistor (R4T, R5T) abnormality
J8
Leak detection thermistor (R15T) abnormality
Subcooling heat exchanger gas pipe thermistor (R6T) abnormality
J9
Receiver gas purge thermistor (R13T) abnormality
JA
High pressure sensor abnormality
JC
Low pressure sensor abnormality
L1
Inverter PCB abnormality
L2
Momentary power failure during test operation
L3
Reactor temperature rise abnormality
L4
Inverter radiation fin temperature rise abnormality
L5
Compressor instantaneous overcurrent
L8
Compressor overcurrent
L9
Compressor startup abnormality
LC
Transmission error between inverter PCB and outdoor unit main PCB
Field Setting from Outdoor Unit