Daikin VRV Aurora RXLQ-TATJU Series Service Manual page 200

Table of Contents

Advertisement

Field Setting from Outdoor Unit
[2-81]:
Change [2-81] to 0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-8].
When [2-81] is set to 0, the original refrigerant temperature target based on [2-8] is kept without
any correction, unless for protection control.
For more information and advice about the effect of these settings, refer to Energy Saving and
Optimum Operation on page 200.
[2-82]:
Change [2-82] to 0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-9].
When [2-82] is set to 0, the original refrigerant temperature target based on [2-9] is kept without
any correction, unless for protection control.
For more information and advice about the effect of these settings, refer to Energy Saving and
Optimum Operation on page 200.
[2-86]:
Note(s)
The setting of [2-86] = 2 saves energy but may increase the time required to reach set point.
193
Cooling comfort setting for VRT control
Default value: 1
Value
[2-81]
0
1 (default)
2
3
Heating comfort setting for VRT control
Default value: 1.
Value
[2-82]
0
1 (default)
2
3
Optional setting to prioritize VRT control
Default value: 0.
Value
[2-86]
0 (default)
2
Cooling comfort setting
Eco
Mild
Quick
Powerful
Heating comfort setting
Eco
Mild
Quick
Powerful
Level
Prioritize largest demand
Prioritize smallest demand
Part 5 Field Settings and Test Operation