Complete the following steps until the problem is solved:
1. Check the XCC event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
correctly installed in place.
3. Make sure that the room temperature is in the range in the operating specifications.
4. Check the XClarity Controller (XCC) event log for any fan- or cooling-related issues.
5. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in
place and correctly installed.
6. Make sure that the room temperature is within operating specifications.
• FQXSPCA0011N: Numeric sensor [NumericSensorElementName] going high (upper non-
recoverable) has asserted.
This message is for the use case when an implementation has detected an Upper Non-recoverable sensor
going high has asserted.
Severity: Error
Serviceable: Yes
Automatically notify Support: No
Alert Category: Critical - Temperature
SNMP Trap ID: 0
CIM Prefix: PLAT CIM ID: 0498
User Action:
1. Check the XCC event log for any fan, cooling or power related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
correctly installed in place.
3. Make sure that the room temperature is in the range in the operating specifications.
• FQXSPCA0013I: Sensor [SensorElementName] has transitioned to normal state.
This message is for the use case when an implementation has detected a Sensor transition to the normal
state.
Severity: Info
Serviceable: No
Automatically notify Support: No
Alert Category: Warning - Temperature
SNMP Trap ID: 12
CIM Prefix: PLAT CIM ID: 0518
User Action:
Information only; no action is required
• FQXSPCA0015J: Sensor [SensorElementName] has transitioned from normal to non-critical state.
This message is for the use case when an implementation has detected a Sensor transitioned to non-
critical from normal.
Severity: Warning
Serviceable: Yes
Automatically notify Support: No
Alert Category: Warning - Temperature
SNMP Trap ID: 12
CIM Prefix: PLAT CIM ID: 0520
30
ThinkSystem SR860 Messages and Codes Reference