Standard Operating Temperature; Expanded Operating Temperature - Dell EMC PowerEdge R240 CHRH4 Installation And Service Manual

Table of Contents

Advertisement

Standard operating temperature

Table 30. Standard operating temperature specifications
Standard operating temperature
Continuous operation (for altitude less than 950 m or 3117
ft)

Expanded operating temperature

Table 31. Expanded operating temperature specifications
Expanded operating temperature
Continuous operation
≤ 1% of annual operating hours
NOTE:
When operating in the expanded temperature range, the performance of the system may be impacted.
NOTE:
When operating in the expanded temperature range, ambient temperature warnings may be reported on the System
Event Log.
Expanded operating temperature restrictions
Do not perform a cold startup of the system below 5°C.
The operating temperature specified is for a maximum altitude of 950m for fresh air cooling.
Four system fans are required.
Support for up to 71W processor.
GPU is not supported.
Non-Dell qualified peripheral cards and/or peripheral cards greater than 25 W are not supported.
Specifications
10–35°C (50–95°F) with no direct sunlight on the equipment.
Specifications
5°C–40°C at 5% to 85% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature
(10°C–35°C), the system can operate continuously in
temperatures as low as 5°C and as high as 40°C.
For temperatures 35°C– 40°C, derate maximum allowable
temperature by 1°C per 175 m (1°F per 319 ft) above 950 m (3,1171
ft).
-5°C–45°C at 5% to 90% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature
(10°C–35°C), the system can operate down to -5°C or
up to 45°C for a maximum of 1% of its annual operating
hours.
For temperatures 40°C– 45°C, derate maximum allowable
temperature by 1°C per 125 m (1°F per 228 ft) above 950 m (3.117
ft).
Technical specifications
117