Servo Simplified Adjustment; First Measure Against Vibration - Mitsubishi M800S Series Connection And Set Up Manual

Hide thumbs Also See for M800S Series:
Table of Contents

Advertisement

M800S/M80/E80 Series Connection and Setup Manual
21 Confirming the Basic Operation

21.3 Servo Simplified Adjustment

21.3.1 First Measure Against Vibration

Setting the filter can reduce the vibration.
(1) Select [Drv mon] and then [Servo unit] on the Diagn screen. See the displayed value in "AFLT frequency".
(Note)
(2) Select [Param] and then [Servo param] on the Mainte screen. Set the AFLT frequency value you saw at (1) to
"#2238 SV038 FHz1 (Notch filter frequency 1)".
(Note)
If the vibration is not reduced by the measure, refer to the manuals of the drive unit you are using.