7.23 Input/output module FDCIO224 [DE]

7.23.1 Installation

Building Technologies
Fire Safety
The input/output module FDCIO224 has four potential-free contact inputs and four
control outputs for VdS-compliant connection of the VdS extinguishing interface.
For this application it must be installed in the fire control panel. The input/output
module is mounted onto the DIN rail.
2
1
Figure 119: Installing the input/output module FDCIO224 in the fire control panel
1
Input/output module FDCIO224
2
DIN rail
3
Mounting feet
1. Insert the two mounting feet (3) at the sides of the input/output module.
2. Push the input/output module (1) with the mounting feet (3) against the DIN rail
(2) until the mounting feet snap into place.
3. Connect the input/output module according to the pin assignment. You will find
the pin assignment in document 007023, Technical Manual.
Installing, exchanging and connecting modules
Input/output module FDCIO224 [DE]
7
1
3
2
201 | 248