Network Module (Safedlink); Installation - Siemens FS720 Mounting & Installation

Fire detection system
Table of Contents

Advertisement

Installing, exchanging and connecting modules
7

Network module (SAFEDLINK)

7.11.2.4 X6 intrusion detection system / local alarm / identification
7.12 Network module (SAFEDLINK)

7.12.1 Installation

128 | 248
Building Technologies
Fire Safety
lamp
Pin
Designation
8
Ke Leuchte +
7
Ke Leuchte -
6
Oertl Alarm +
5
Oertl Alarm -
4
-
3
2
1
Admissible cable cross-section: 0.2...1.5 mm²
Ke Leuchte +
Ke Leuchte -
Oertl Alarm +
Oertl Alarm -
1*
Horn or beacon
2*
FSD sabotage, connection for "Transmission intrusion detection system"
(can be connected as NO or NC)
3*
If necessary
This component is installed in exactly the same way as for the operating units
with the PMI & mainboard FCM2004 and the PMI & mainboard FCM2027.
If you are installing only one network module (SAFEDLINK) FN2001-A1, you must
do so in the left-hand slot (X13).
When two network modules are used (SAFEDLINK) FN2001-A1, installation is
identical for both.
Description
Identification lamp (+)
Identification lamp (-)
Local alarm (+)
Local alarm (-)
Not used
FSD sabotage, closer (normally open)
FSD sabotage, common
FSD sabotage, opener (normally open)
X6
8
+
-
7
6
+
Ω
Ω
40 ... 2k
-
5
4
2*
3
2
2
2*
1
300mA / max. 7.5W
1*
Ω
3*
3*
560
2W
A6V10210390_m_en_--
2018-08-29