Siemens FS720 Mounting & Installation page 76

Fire detection system
Table of Contents

Advertisement

Mounting and installing extinguishing control panels
6
Extinguishing terminal installation and wiring
6.4.2.3 External power supply, connector X2
76 | 248
Building Technologies
Fire Safety
If the extinguishing terminal is supplied with power by an external power supply,
ground fault monitoring must be switched on.
Connector X2, supply
PIN
Designation
1
VSYS_POS
2
VSYS_POS
3
VSYS_NEG
4
VSYS_NEG
5
#MAINS
6
#BATTERY
7
-3SRC
8
+3SRC
FP2015
X2
#BATTERY
#MAINS
VSYS +
+
VSYS -
-
BATT +
F3
+
-
BATT -
External housing
Figure 41: Wiring diagram of an external terminal with external power supply
Description
Supply input V+
Supply output V+ (looped through)
Supply input V-
Supply output V- (looped through)
Network monitoring connection
Battery monitoring connector
Supply input V-, 3rd source of voltage
Supply input V+, 3rd source of voltage
8
7
6
5
4
3
2
1
2x 12 V
Extinguishing terminal
VSYS_POS
1
+
VSYS_POS
2
+
VSYS_NEG
-
3
-
VSYS_NEG
4
5
#MAINS
#BATTERY
6
7
-3SRC
-
+
8
+3SRC
1x 9 V
A6V10210390_m_en_--
2018-08-29
X2

Advertisement

Table of Contents
loading

Table of Contents