7.3.2.2 X5 monitored horn outputs 1 and 2
7.3.2.3 X6 alarm and fault monitored outputs
Building Technologies
Fire Safety
Pin
Designation
4
SOUND2-
3
SOUND2+
2
SOUND1-
1
SOUND1+
Admissible cable cross-section: 0.2...1.5 mm²
SOUND2-
-
SOUND2+
F403
+
SOUND1-
-
SOUND1+
F400
+
Pin
Designation
4
FAU_OUT
3
VSYS_O
2
AL_OUT-
1
AL_OUT+
Admissible cable cross-section: 0.2...1.5 mm²
1
Remote transmission
Installing, exchanging and connecting modules
Description
Horn output 2 (-)
Horn output 2 (+)
Horn output 1 (-)
Horn output 1 (+)
X5
4
2.3 ... 5.5 kΩ
3
2
2.3 ... 5.5 kΩ
1
Description
Output fault
Supply output for consumer fault
Alarm output (-)
Alarm output (+)
Periphery board (4 loops)