INPUT_COL_MON_1+
INPUT_COL_MON_1-
Building Technologies
Fire Safety
Circuitry example
DM1103-L / DM1103-S
Device 1
Figure 30: Collective monitored input with 'Manual release' and 'Emergency hold'
EOL resistor: 18 V voltage reference diode / bidirectional / min. 600 W (e.g.,
P6KE18CA)
Max. line resistance, both conductors: 80 Ω
Mounting and installing extinguishing control panels
Card cage connections (1 sector exting.) FCA2046
DM1103-L / DM1103-S
Device 8