Siemens FS720 Mounting & Installation page 137

Fire detection system
Table of Contents

Advertisement

Building Technologies
Fire Safety
(SAFEDLINK). You will find information in the description of network module
(SAFEDLINK) FN2001.
Fire control panel
Vsys+
Vsys-
Periphery board
FCI2002 / FCI2004
Figure 71: Example of wiring the FN2006 / FN2007 to the FN2001 for internal installation
The total cable lengths of the electric C-WEB connections with copper cables for
all fiber network modules to the stations may be no longer than 1000 m.
NOTICE
Wiring cross-wise in the electrical C-WEB
If the FN2001 is wired cross-wise to the FN2006/FN2007, ground fault monitoring
is not required. The wiring must be carried out 1:1 according to the diagram
above (A1-A1, B1-B1, A2-A2, and B2-B2).
Installing, exchanging and connecting modules
Installing the fiber optic cable network module
FN2006/FN2007
1
A1
EF 1
-
A1
B1
B1
A2
B2
A2
1
EF 2
-
B2
X1
7
+
1
Power A
8
-
9
C
10
NO
NC
+
1
Power B
-
C
NO
NC
7
Line 1
Line 2
137 | 248
A6V10210390_m_en_--
2018-08-29