Installing, exchanging and connecting modules
7
Module bus cards
7.18.2.4 Connection terminals of line card (SynoLOOP) in card cage
182 | 248
Building Technologies
Fire Safety
The line card (SynoLOOP) FCL7201-Z3 determines the PIN assignment of the four
connection terminals in the card cage.
External connections on the card cage using the example of module bus card 1
with the associated connection terminals X11 and X12:
X12
4
3
2
1
4
3
8
7
6
5
8
7
The external connections of module bus card 2 are on connection terminals
X21 and X22
The external connections of module bus card 3 are on connection terminals
X31 and X32
The external connections of module bus card 4 are on connection terminals
X41 and X42
The external connections of module bus card 5 are on connection terminals
X51 and X52
Depending on the card cage, not all slots may be available for module bus cards
and connection terminals. However, the numbering and assignment of the
connection terminals are identical on all card cages.
Connector Pin
Signal
X11
1
IO_1
2
IO_2
3
IO_3
4
IO_4
X12
1
IO_5
2
IO_6
3
IO_7
4
IO_8
X11
5
IO_9
6
IO_10
7
IO_11
8
IO_12
X12
5
IO_13
6
IO_14
7
IO_15
8
IO_16
Admissible cable cross-section: 0.2...1.5 mm²
Only one stub may be connected to each of the connections C1x to C4x.
1
X11
2
1
6
5
Connection
Loop
C11_POS
Loop 1
C11_NEG
C12_POS
C12_NEG
C21_POS
Loop 2
C21_NEG
C22_POS
C22_NEG
C31_POS
Loop 3
C31_NEG
C32_POS
C32_NEG
C41_POS
Loop 4
C41_NEG
C42_POS
C42_NEG
Stub
Stub 1
(Stub 1)
1
Stub 2
(Stub 2)
1
Stub 3
(Stub 3)
1
Stub 4
(Stub 4)
1
A6V10210390_m_en_--