Siemens FS720 Mounting & Installation page 74

Fire detection system
Table of Contents

Advertisement

Mounting and installing extinguishing control panels
6
Extinguishing terminal installation and wiring
6.4.2.2 Secondary extinguishing terminal, connections X1, X2
74 | 248
Building Technologies
Fire Safety
Connector X2, supply
PIN
Designation
1
VSYS_POS
2
VSYS_POS
3
VSYS_NEG
4
VSYS_NEG
5
#MAINS
6
#BATTERY
7
-3SRC
8
+3SRC
Connector X1, RS485 connection
PIN
Designation
1
DATA_A
2
DATA_A
3
DATA_B
4
DATA_B
Admissible cable cross-section: 1.5... 1.5 mm²
Description
Supply input V+
Supply output V+ (looped through)
Supply input V-
Supply output V- (looped through)
Network monitoring connection
Battery monitoring connector
Supply input V-, 3rd source of voltage
Supply input V+, 3rd source of voltage
Description
Terminal line +
Terminal line + (looped through)
Terminal line -
Terminal line - (looped through)
A6V10210390_m_en_--
2018-08-29

Advertisement

Table of Contents
loading

Table of Contents