Siemens FS720 Mounting & Installation page 54

Fire detection system
Table of Contents

Advertisement

Mounting and installing extinguishing control panels
6
Card cage connections (1 sector exting.) FCA2046
6.2.1.4 X11, collective monitored inputs
54 | 248
Building Technologies
Fire Safety
Collective devices ('manual release' or 'emergency hold') can be connected to
inputs 1...4; a max. of 8 devices per input.
The inputs can also be used as monitored standard inputs. They can be configured
to the different monitoring functions. All inputs offer 2-way monitoring.
9
16
1
8
Figure 29: FCA2046 connection X11/9-16
PIN Designation
9
INPUT_COL_MON_1
+
10
INPUT_COL_MON_1
-
11
INPUT_COL_MON_2
+
12
INPUT_COL_MON_2
-
13
INPUT_COL_MON_3
+
14
INPUT_COL_MON_3
-
15
INPUT_COL_MON_4
+
16
INPUT_COL_MON_4
-
Admissible cable cross-section: 0.2... 1.5 mm²
INPUT_COL_MON_1
X11
INPUT_COL_MON_1
INPUT_COL_MON_2
INPUT_COL_MON_2
INPUT_COL_MON_3
INPUT_COL_MON_3
INPUT_COL_MON_4
INPUT_COL_MON_4
X11
Color
Description
Orange Input 1+, collective, monitored
Orange Input 1-, collective, monitored
Orange Input 2+, collective, monitored
Orange Input 2-, collective, monitored
Orange Input 3+, collective, monitored
Orange Input 3-, collective, monitored
Orange Input 4+, collective, monitored
Orange Input 4-, collective, monitored
+
9
-
10
+
11
-
12
+
13
-
14
+
15
-
16
A6V10210390_m_en_--