7.2.2.2 X6 Horn, alarm and fault monitored outputs
7.2.2.3 X7 RT alarm and RT fault changeover contacts
Building Technologies
Fire Safety
Pin
Designation
6
FAU_OUT
5
VSYS_O
4
AL_OUT-
3
AL_OUT+
2
SOUND1-
1
SOUND1+
Admissible cable cross-section: 0.2...1.5 mm²
1
Remote transmission
Pin
Designation
6
FAU_NC
5
FAU_COM
4
FAU_NO
3
AL_NC
2
AL_COM
1
AL_NO
Admissible cable cross-section: 0.2...1.5 mm²
1
Remote transmission
FAU_...
Diagram of relay in ↑ normal operation = contact 5/4 closed
AL_...
Diagram of relay in normal operation = contact 2/3 closed
Installing, exchanging and connecting modules
Description
Output fault
Supply output for consumer fault
Alarm output (-)
Alarm output (+)
Horn output (-)
Horn output (+)
Description
↑ RT fault ↑ normally closed contact
RT fault center tap (common)
RT fault ↑ normally open contact
RT alarm break contact (normally closed)
RT alarm center tap (common)
RT alarm make contact (normally open)
Periphery board (2-loop)