Finalizing the Installation

Mantel Requirements

Combustible Mantels

Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured
from the face of the fireplace) must fall in the shaded portion of the table.
Any material that protrudes more than 3/4" (19mm) from the non-combustible facing is considered a
mantel and must meet the mantel requirements.
Mantel Height
Above Base of
Fireplace (a)
Top of Fireplace
(not stand-off)
Mantel (combustible or non-
combustible)
© Travis Industries
Maximum Mantel Depth (b)
39"+(991mm+)
38"(965mm)
37"(940mm)
36"(914mm)
35"(889mm)
34"(864mm)
33"(838mm)
NOTE: No combustibles may be
installed in front of fireplace.
b
a
Base of the Fireplace
5/8/2019 - 1505
(for qualified installers only)
Combustible mantel columns (legs) must
be placed to the side of the fireplace face.
Non-combustible mantel columns do not
have a minimum clearance.
564 GSR2 25K CF