Finalizing the Installation

Top Vent Configuration with Vertical Termination

The termination must fall
within the shaded area
shown in the chart. Use
the indicated restrictor
and diffuser positions.
Up to four elbows (45° or
90°) may be used.
Only one horizontal
elbow may be used.
Use 6-5/8" diameter
vent. Attach the 8" to 6-
5/8" reducer (Travis part
# 98900165) to the
fireplace.
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
© Travis Industries
40' max (12m)
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
H2
H1
5/8/2019 - 1505
(for qualified installers only)
Exhaust Restrictor # 5
Intake Restrictor # 2
Diffuser Position # 2
Exhaust Restrictor # 4
Intake Restrictor # 2
Diffuser Position # 2
Exhaust Restrictor # 3
Intake Restrictor # 2
Diffuser Position # 2
Exhaust Restrictor # 2
Intake Restrictor # 1 (stock)
Diffuser Position # 2
Attach 6-5/8" Reducer
Directly to Fireplace
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
This is considered a
vertical elbow
31
40' max (12m)
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
564 GSR2 25K CF