CORRELATION BETWEEN GAS PRESSURE AND BURNER OUTPUT
To obtain the maximum output, a gas head pressure of 9.3 mbar, relatively to 916T1 model, is measured
(M2, see chapter 3.6, page 7) with the combustion chamber at 0 mbar using gas G20 with a net heat value
of 10 kWh/m
(8.570 kcal/m
3
12
10
8
6
4
2
0
0
0
3.
INSTALLATION
THE BURNER MUST BE INSTALLED IN CONFORMITY WITH LEGISLATION AND LOCAL STANDARDS.
3.1
WORKING POSITION
The burner is designed for operation in position 1 only.
Installation in positions 2, 3, 5, 6 and 7 is not recommended as it is likely to hinder the unit's proper operation
since air damper closure cannot be guaranteed when the burner is on standby.
Installation in position 5 is only possible using the "MULTIBLOC rotation kit", to be ordered separately.
Installation 4 is prohibited as safety is compromised.
1
5
3115
).
3
50
100
100,000
50,000
2
6
150
150,000
Thermal power
3
7
5
GB
D8952
200
250
kW
200,000
kcal/h
4
D4450