Section 5 • Compressor Control
This quantity is used for fine adjustment, and this
setpoint is used to smooth out process variations.
This setpoint should be set high enough to prevent
hunting but low enough to prevent control system
overshoot.
D = Derivative (rate) setpoint:
Used to adjust the load control action, account-
ing for how fast the error is changing, positively or
negatively. It´s a standard PID loop variable, and it
is not used for our applications.
Interval:
This setpoint defines the time interval for calcula-
tion of Integral Error.
Figure 5-13. Compressor Control Screen – Pumpdown Control
5 – 14

Pumpdown Control

The Pumpdown Control defines a method of "pumping"
down a chiller, which is to draw off refrigerant from it.
This feature can be enabled or disabled from this page,
see Figure 5-13. If Pumpdown is enabled, this feature
will only function when the compressor is running in lo-
cal Auto Mode and Control Mode Configured is Suction
Pressure.
If the Pumpdown Operation is running, then;
• The
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Auto-cycle
functionality
Pumpdown mode will cause the compressor to
cycle off via the Pumpdown Stop Pressure set-
point. Normally, the Pumpdown Stop Pressure
setpoint will be set lower than the Auto-cycle
Stop setpoint. Therefore, as the suction pressure
is pulled down, the compressor is prevented from
shutting down prematurely via the Auto-cycle
Stop setpoint by automatically ignoring the Auto-
cycle feature.
is
ignored.