Appendix B • Communication Tables
Ethernet IP
Modbus
Address
Address
N65:12
40412
Low Process Temperature Trip Setpoint #2
High Process Temperature Alarm Setpoint
N65:13
40413
#2
N65:14
40414
Low Process Pressure Alarm Setpoint #1
N65:15
40415
Low Process Pressure Trip Setpoint #1
N65:16
40416
High Process Pressure Alarm Setpoint #1
N65:17
40417
High Process Pressure Trip Setpoint #1
N65:18
40418
Low Process Pressure Alarm Setpoint #2
N65:19
40419
Low Process Pressure Trip Setpoint #2
N65:20
40420
High Process Pressure Alarm Setpoint #2
N65:21
40421
High Process Pressure Trip Setpoint #2
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Table B-18. Alarms/Trips Block (Page 1) (2 of 2)
Alarms/Trips (Page 1)
Data Type
Value
Mode
Read-
F-INT
Write
Read-
F-INT
Write
(Currently
Read-
F-INT
Unused)
Write
(Currently
Read-
F-INT
Unused)
Write
(Currently
Read-
F-INT
Unused)
Write
(Currently
Read-
F-INT
Unused)
Write
(Currently
Read-
F-INT
Unused)
Write
(Currently
Read-
F-INT
Unused)
Write
(Currently
Read-
F-INT
Unused)
Write
(Currently
Read-
F-INT
Unused)
Write
Lower
Higher
Range
Range
-100
210
-100
210
-15
300
-15
300
-15
350
-15
350
-15
300
-15
300
-15
300
-15
300
B − 13