Section 19 • Compressor Sequencing

Status Symbols

Compressor Sequencing status symbols are automati-
cally refreshed every second. For symbols see Table 19-1.
Before configuring the sequencing table on the
compressor, log on to the other compressors
one by one and put each compressor in Stand-By
mode. Then wait till other compressors show up
under detected devices pop-screen in page 3. Add
compressors which in turn will get shown in Device
list screen and also in Equipment list.
Symbol
19 – 2
NOTE

Table 19-1. Status Symbols

Default, if Compressor is not present.
Compressor is configured in sequencing table but is not
configured in "Seq Stand-By" mode or is not detected in
network or compressor sequencing table configuration
or control mode is not correct or Compressor is waiting in
Anti-recycle or Run Permissive.
Compressor configured in sequencing table and is in
ready to run state.
Compressor is running with Alarm / Load Limit condition.
Compressor stopped due to Error Condition.
Compressor running at maximum capacity or in partially
loaded state without any error.
Compressor active.
Compressor running into its stop timer, will be stopped.
Compressor running into its start timer, will be started.
Compressor is next in sequence for unloading.
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3