Appendix B • Communication Tables
Ethernet IP
Modbus
Address
Address
Control Setpoint #1 (Suction Press,
N57:0
40200
Process Control, Discharge Press)
Load Offset Setpoint #1 (Suction
N57:1
40201
Press, Process Control, Discharge
Press)
Load Interval Setpoint #1 (Suction
N57:2
40202
Press, Process Control, Discharge
Press)
Unload Offset Setpoint #1 (Suction
N57:3
40203
Press, Process Control, Discharge
Press)
Unload Interval Setpoint #1 (Suction
N57:4
40204
Press, Process Control, Discharge
Press)
Control Setpoint #2 (Suction Press,
N57:5
40205
Process Control, Discharge Press)
Load Offset Setpoint #2 (Suction
N57:6
40206
Press, Process Control, Discharge
Press)
Load Interval Setpoint #2 (Suction
N57:7
40207
Press, Process Control, Discharge
Press)
Unload Offset Setpoint #2 (Suction
N57:8
40208
Press, Process Control, Discharge
Press)
Unload Interval Setpoint #2 (Suction
N57:9
40209
Press, Process Control, Discharge
Press)
N57:10
40210
IO Based Setpoint Control
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Table B-11. Compressor Control Setpoints Block
Compressor Control Setpoints
Data Type
Value
F-INT
F-INT
INT
F-INT
INT
F-INT
F-INT
INT
F-INT
INT
0 = Disable
INT
1 = Enable
Lower
Higher
Mode
Range
Range
(-15.0,
(150.0,
Read-
-100.0,
300.0,
Write
-15.0)
400.0)
(150.0,
Read-
(0.1, 0.1,
300.0,
Write
0.5)
20.0)
Read-
(600,
(1, 1, 1)
Write
600, 5)
(150.0,
Read-
(0.1, 0.1,
300.0,
Write
0.5)
20.0)
Read-
(600,
(1, 1, 1)
Write
600, 5)
(-15.0,
(150.0,
Read-
-100.0,
300.0,
Write
-15.0)
400.0)
(150.0,
Read-
(0.1, 0.1,
300.0,
Write
0.5)
20.0)
Read-
(600,
(1, 1, 1)
Write
600, 5)
(150.0,
Read-
(0.1, 0.1,
300.0,
Write
0.5)
20.0)
Read-
(600,
(1, 1, 1)
Write
600, 5)
Read
NA
NA
B − 9