Section 6 • Alarms and Trips
Warnings
Not Running (Idle)

Analog Aux In 8:

Below messages will be displayed when Analog Aux In 8 satisfy safety conditions.
Warnings are displayed in IDLE condition and it is monitored under Inhibit Checkbox (Refer Figure 6-5)
When "Neither" is selected in Alarm/Trip then No Alarm and Trip for Analog Aux In 8 is monitored.
Alarm condition occurs if the value of a parameter drops below or rises above the configured Alarm setpoint for a
continuous delay time (default 5 seconds).
Trip condition occurs if the value of a parameter drops below or rises above the configured Trip setpoint for a con-
tinuous delay time (default 5 seconds).
Analog Aux In 8 Warning
Inhibit Checked and
Analog Aux In 8 <= Low
Alarm
Inhibit Checked and
Analog Aux In 8 >= High
Alarm
6 – 20
Inhibits
Pre-Start
Analog Aux In 8 Inhibit
Inhibit Checked and
Analog Aux In 8 <= Low
Alarm
Inhibit Checked and
Analog Aux In 8 >= High
Alarm
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Alarms
Running
Analog Aux In 8 Alarm
"Only Alarm" and Analog
Aux In 8 <= Low Alarm
"Only Alarm" and Analog
Aux In 8 >= High Alarm
"Both" and Analog Aux In 8
<= Low Alarm
"Both" and Analog Aux In 8
>= High Alarm
Trips
Running
Analog Aux In 8 Trip
"Only Trip" and Analog Aux
In 8 <= Low Trip
"Only Trip" and Analog Aux In
8 >= High Alarm
"Both" and Analog Aux In 8
<= Low Trip
"Both" and Analog Aux In 8
>= High Trip