Section 5 • Compressor Control
Auto Cycle Process Temperature
Enable: Enables the Auto cycle control. Uncheck
the box to disable the Auto cycle setpoints.
Start Temperature: When the process temperature
is equal to or greater than this setpoint, the com-
pressor will start.
Start Delay: Before the compressor start, there is a
delay for the set time to ensure that process tem-
perature remains equal to or greater than the "Start
Temperature".
Stop Pressure: When the process temperature is
less than or equal to this setpoint, the compressor
will stop.
Stop Delay: Before the compressor stop, there is
a delay for the set time to ensure that the process
temperature remains less than or equal to the "Stop
Temperature".
Figure 5-6. Compressor Control Screen – Auto Cycle (Process Temperature)
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
• Min. Load Shutdown Timer: Enables the Min. Load
Shutdown Timer functionality. Uncheck the box to
disable the Min. Load Shutdown Timer setpoint and
functionality.
This timer is visible and functional only when the
cylinders and unloaders are configured with 100%
unload configuration. If the Compressor is 100% un-
loaded continuously for this amount of time then the
compressor will stop on Auto-Cycle.
5 – 7