Top Status Bar

The standard view of the status bar displays the follow-
ing information. From Left to Right, bar shows Control
Method, Current Run Mode & the difference between
the desired control setpoint and actual value of the pro-
cess variable. See Figure 3-2.
The Top Status Bar also displays the information that re-
quires user attention or intervention. This information is
displayed by highlighting it in different color or by flash-
ing the additional information bars over standard status
bar view.
Standard Bar - Black
The Standard Bar with Black color indicates the condi-
tion where the compressor motor is not running.
Standard Bar - Green
The Standard Bar with Green color displays the informa-
tion that the compressor motor is currently running.
Information Bars will flash their information over the top
of the status bar. The user will see the status bar and then
one or more information bars in a repetitive sequence.
3 – 2
Information Bar - Black
The Information Bar with Black color displays the opera-
tional modes, which are different than the normal run-
ning condition. For example, the load limit condition.
The compressor is unable to completely load due to
some setpoint conditions, like high motor current. This
is notified on the information bar with black color.
Information Bar - Yellow
The Information Bar with Yellow color displays the alarm
conditions. Alarm conditions do not stop the compres-
sor, but these are alerts to the operator that if they do
not take any corrective action, this can result in a com-
pressor trip.
Information Bar - Red
The Information Bar with Red color displays the infor-
mation that the compressor motor was stopped due to
the condition listed on the Information Bar. Compressor
trips are designed to protect the equipment and any
personnel operating the equipment.

Figure 3-2. Top Status Bar