Section 13 • Data Backup
Restore Original Database to New SD card
Now that the new card is inserted, power up the
MicroVission panel. The MicroVission boots up in a min-
ute or so.
Once the MicroVission is booted up, press on the
"User Access" button.
Insert the thumb drive in to the USB port.
Navigate to the Data Backup screen. You should
again see the USB thumb drive listed in the "Available
Devices" window.
Select the Load function (above the "Available
Devices" field), and then highlight the device that is
listed in the "Available Devices" window.
In the "Select Folder/File" window, find the backup
file for this compressor, and highlight it.
Now press the "Load" button.
a. A pop-up window will appear with a message
Loading new databases will require a pro-
gram restart. Continue?". Press "Yes".
b. b. Another pop-up window might appear with a
Another pop-up window might appear with a
message "One or more settings selected for
message "One or more settings selected for
loading were missing from the archive. And it
loading were missing from the archive. And it
will list what is missing. Continue loading any-
will list what is missing. Continue loading any-
way?". Press "Yes".
way?". Press "Yes".
c. c. Another pop-up box might appear with a
Another pop-up box might appear with a
message asking if you want to use the IP ad-
message asking if you want to use the IP ad-
dress it found. Press "OK".
dress it found. Press "OK".
A pop-up box appears with a message "Settings
were successfully loaded. Program will restart".
Press "OK".
When the OK button is pressed, the panel will reboot.
Now using the "hand documented" settings that you re-
corded, compare the setpoints on that list against those
in the MicroVission. They should all be OK. Here are the
KNOWN issues that we have found with this procedure.
If you have communication connection issues after
restoring the database, you may have to "re-enter"
the IP address that is shown on page 3 of the con-
figuration screen. If you experience problems after
the "Restore" function – then re-enter your commu-
nication settings.
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Record Operating Setpoints And Configuration
Information
Before powering down the MicroVission to replace the
SD card, copy the following operating setpoints and
configuration information.
1. Configuration Screen - Page 1
a. No. of Cylinders and No. of Unloaders.
b. Compressor Control Type & Number of
Controllers.
c. Oil Monitoring Settings.
d. Anti-Recycle Settings.
2. Configuration Screen - Page 2
a. Order Number.
3. Configuration Screen - Page 3
a. Active Remote Control Setting.
b. If Active Remote Control = Direct I/O, docu-
ment "type" of Direct I/O selection.
c. Ethernet Settings.
4. Configuration Screen, Page 5
a. Optional I/O boards.
5. Compressor Control Setpoints – all.
6. Alarms and Trips Setpoints – all.
7. Timer Setpoints – all.
8. Instrument Calibration, Pressure page
a. Record Transducer Range selection for
Suction Pressure, Discharge Pressure, Oil
Pressure, Filter Inlet Pressure & Filter Outlet
Pressure.
b. Record 'Total Offset" value for Suction
Pressure, Discharge Pressure, Oil Pressure,
Filter Inlet Pressure & Filter Outlet Pressure.
9. Instrument Calibration - Temperature page
a. Record Transducer Range selection for Suction
Temperature, Discharge Temperature, Oil
Temperature & Process Temperature.
b. Record "Total Offset" value for Suction
Temperature, Discharge Temperature, Oil
Temperature & Process Temperature.
10. Instrument Calibration – Motor Current Settings.
11. Compressor Runtime.
13 – 5