Emerson Rosemount 3051P Reference Manual page 20

In-line pressure transmitter with hart protocol
Hide thumbs Also See for Rosemount 3051P:
Table of Contents

Advertisement

Configuration
April 2020
Setting pressure units with a local operator interface (LOI)
Procedure
1. Follow
2. Use the SCROLL and ENTER buttons to select desired unit.
3. Save by selecting SAVE as indicated on the LCD display screen.
Example
Figure 2-6: Selecting Units with LOI
2.8.2
Reranging the transmitter
The range values command sets each of the lower and upper range analog values to a
pressure. The lower range point represents 0 percent of range and the upper range point
represents 100 percent of range.
In practice, the transmitter range values may be changed as often as necessary to reflect
changing process requirements.
Select from one of the methods below to rerange the transmitter. Each method is unique;
examine all options closely before deciding which method works best for your process.
Rerange by manually setting range points with a Field Communicator, AMS Device
Manager, or local operator interface (LOI).
Rerange with a pressure input source and a Field Communicator, AMS Device Manager,
LOI, or local zero and span buttons.
Manually rerange the transmitter by entering range points
Entering range points with a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
20
Figure 2-6
to select desired pressure and temperature units.
Reference Manual
00809-0700-4001
2, 2, 2, 1
Emerson.com/Rosemount

Advertisement

Table of Contents
loading

Table of Contents