Electrical installation
April 2020
Figure 4-7: Wiring Pair and Ground
A. Insulate shield and shield drain wire.
B. Insulate exposed shield drain wire.
C. Terminate cable shield drain wire to earth ground.
Transmitter case grounding
The most effective transmitter case grounding method is a direct connection to earth
ground with minimal impedance.
WARNING
Always ground the transmitter case in accordance with national and local electrical codes.
Methods for grounding the transmitter case include:
•
Internal ground connection: the internal ground connection screw is inside the FIELD
TERMINALS side of the electronics housing. This screw is identified by a ground symbol
( ). The ground connection screw is standard on all Rosemount 3051P Transmitters.
Refer to
60
A
DP
B
C
Figure
4-8.
Reference Manual
00809-0700-4001
Emerson.com/Rosemount