Reference Manual
00809-0700-4001
Figure 4-1: LOI Display Assembly
A. LCD/LOI display
B. Extended cover
C. Captive screws
4.3.1
Rotate LCD/local operator interface (LOI) display
Procedure
1. Secure the loop to manual control and remove power to transmitter.
2. Remove transmitter housing cover.
3. Remove screws form the LCD/LOI display and rotate to desired orientation.
4. Re-insert screws.
5. Reattach transmitter housing cover.
6. Reattach power and return loop to automatic control.
Rosemount 3051P
a) Insert 10-pin connector into the display board for the correct orientation.
Carefully align pins for insertion into the output board.
WARNING
Explosions
Cover must be fully engaged to comply with explosion proof requirements.
Electrical installation
April 2020