3. Follow screen prompts to configure alarm and saturation levels.
Configuring alarm and saturation levels using a local
operator interface (LOI)
Procedure
Refer to
Figure 2-11: Configuring Alarm and Saturation with LOI
2.10.2
Configuring scaled variable
With the scaled variable, you can create a relationship/conversion between the pressure
units and user-defined/custom units.
There are two use cases for scaled variable:
1. Allow custom units to be displayed on the transmitter's LCD/local operator interface
2. Allow custom units to drive the transmitters 4-20 mA output.
If the you want custom units to drive the 4–20 mA output, re-map the scaled variable as
the primary variable. Refer to
The scaled variable configuration defines the following items:
Scaled variable units
Scaled data options
Pressure value position 1 Lower known value point with consideration of linear offset.
Scaled variable position 1 Custom unit equivalent to the lower known value point.
Pressure value position 2 Upper known value point.
Scaled variable position 2 Custom unit equivalent to the upper known value point.
Linear offset
Rosemount 3051P
Figure 2-11
for instructions to configure alarm and saturation levels.
(LOI) display.
Re-mapping device
Custom units to be displayed.
Defines the transfer function for the application.
The value required to zero out pressures affecting the
desired pressure reading.
variables.
Configuration
April 2020
27