Advertisement

Operation and maintenance
April 2020
5.6.3
Recalling factory trim—analog output
The Recall Factory Trim—Analog Output command allows the restoration of the as-
shipped factory settings of the analog output trim.
This command can be useful for recovering from an inadvertent trim, incorrect plant
standard or faulty meter.
Recall factory trim - analog output with a Field
Communicator
Procedure
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field
Communicator to complete the digital to analog trim using other scale.
Device Dashboard Fast Keys
Recall factory trim - analog output with AMS Device
Manager
Procedure
1. Right click the device and, under the Method drop down menu, move the cursor
2. Select Next to set the control loop to manual.
3. Select Analog Output Trim under Select Trim to recall and click Next.
4. Follow screen prompts to recall analog output trim.
Recall factory trim - analog output with local operator
interface (LOI)
Procedure
Reference
Figure 5-7: Recall Factory Trim – Analog Output with LOI
74
over Calibrate and select Restore Factory Calibration.
Figure 5-7
for LOI instructions.
Reference Manual
00809-0700-4001
3, 4, 3
Emerson.com/Rosemount