Changing a transmitter address
To activate multidrop communication, assign the transmitter poll address to a number
from 1 to 15 for HART
multidropped loop must have a unique poll address.
Changing transmitter address using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Changing transmitter address using AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. In HART
3. In HART Revision 7 mode:
4. Carefully read the warning and click Yes if it is safe to apply the changes.
2.13.2
Communicating with a multidropped transmitter
To communicate with a multidrop transmitter you must set up the Field Communicator or
AMS Device Manager for polling.
Communicating with a multidropped transmitter using a
Field Communicator
Procedure
1. Select Utility and Configure HART Application.
2. Select Polling Addresses.
3. Enter 0–63.
Rosemount 3051P
®
Revision 5, and 1 to 63 for HART Revision 7. Each transmitter in a
®
Revision 5 mode:
a) Select Manual Setup and then select the HART tab.
b) In the Communication Settings box enter polling address in the Polling
Address box and then select Send.
a) Select Manual Setup, select the HART tab, and select the Change Polling
Address button.
®
HART
Revision 5
HART Revision 7
2, 2, 5, 2, 1
2, 2, 5, 2, 2
Configuration
April 2020
35