Figure 4-5: Load Limitation
Maximum loop resistance = 43.5 x (Power supply voltage – 10.5)
The total resistance load is the sum of the resistance of the signal leads and the load
resistance of the controller, indicator,intrinsically safe (I.S.) barriers, and related pieces. If
intrinsic safety barriers are used, the resistance and voltage drop must be included.
4.6.3
Wiring the transmitter
CAUTION
Incorrect wiring can damage test circuits.
Do not connect the power signal wiring to the test terminals.
Note
Use shielded twisted pairs to yield best results. To ensure proper communication, use 24
AWG or larger wire and do not exceed 5,000 ft. (1500 m).
Rosemount 3051P
Electrical installation
April 2020
57