Hardware installation
April 2020
Figure 3-2: Head Markings
A. Carbon steel (CS) head markings
B. The last digit in the F593_ head marking may be any letter between A and M.
C. Stainless steel (SST) head markings
D. Alloy K-500 head marking
3.4.2
Impulse piping
Mounting requirements
Impulse piping configurations depend on specific measurement conditions.
Refer to
configurations:
Liquid measurement
Place taps to the side of the line to prevent sediment deposits on the transmitter's
process isolator.
Mount the transmitter beside or below the taps so gases can vent into the process line.
Mount drain/vent valve upward to allow gases to vent.
42
Figure 3-3
through
Figure 3-5
for examples of the following mounting