Emerson Rosemount 3051P Reference Manual page 29

In-line pressure transmitter with hart protocol
Hide thumbs Also See for Rosemount 3051P:
Table of Contents

Advertisement

Reference Manual
00809-0700-4001
2.10.3
Re-mapping device variables
The re-mapping function allows you to configure the transmitter primary, secondary,
tertiary, and quaternary variables (PV, 2V, 3V, and 4V) as desired.
You can re-map the PV with a Field Communicator, AMS Device Manager, or a local
operator interface (LOI). You can only re-map variables 2V, 3V, and 4V via Field
Communicator or AMS Device Manager.
Note
The variable assigned to the primary variable drives the 4–20 mA output. This value can be
selected as Pressure or Scaled Variable. The 2, 3, and 4 variables only apply if using HART
burst mode.
Re-map device variables using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Fast Keys
Re-map device variables using AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup and click on the HART tab.
3. Assign Primary, secondary, tertiary, and quaternary variables under Variable
4. Select Send.
5. Carefully read the warning and select Yes if it is safe to apply the changes.
Re-map device variables using local operator interface (LOI)
Procedure
Refer to
Rosemount 3051P
Mapping.
Figure 2-13
for instructions on re-mapping the primary variable using an LOI.
2, 1, 1, 3
Configuration
April 2020
®
29