A recent change has been made to the device by a secondary HART
handheld device.
Recommended actions
Analog output fixed
LCD display
screen
Local operator
interface (LOI)
screen
The analog output is fixed and does not represent the process measurement.
This may be caused by other conditions in the device or because the device has been set to
loop test or multidrop mode.
Recommended actions
Simulation active
LCD display
screen
Rosemount 3051P
1. Check the connection between the LCD and the circuit board.
2. Replace the LCD display.
3. Replace the electronics board.
4. Replace the pressure transmitter.
(None)
(None)
1. Verify that the configuration change of the device was intended and expected.
2. Clear this alert by selecting Clear Configuration Changed Status.
3. Connect a HART master, such as AMS or similar, which will autmatically clear
the alert.
ANLOG FIXED
ANALOG FIXED
1. Take action on any other notifications from the device.
2. If the device is in a loop test and should no longer be, disable or momentarily
remove power.
3. If the device is in multidrop mode and should not be, re-enable loop current by
setting the polling address to 0.