Safety instrumented systems requirements
April 2020
7.6.4
Safety instrumented systems (SIS) reference
Operate the transmitter in accordance to the functional and performance specifications
provided in the
7.6.5
Failure rate data
The
FMEDA Report
7.6.6
Failure values
Safety Deviation (defines what is dangerous in an FMEDA): ±2.0% of analog output span
Transmitter response time: provided in
Interval: At least once every 60 minutes.
7.6.7
Product life
50 years: based on worst case component wear-out mechanisms, not based on wear-out
of process wetted materials.
96
Rosemount 3051P Product Data
includes failure rates.
Dynamic
Reference Manual
00809-0700-4001
Sheet.
performance. Self-diagnostics Test
Emerson.com/Rosemount