Reference Manual
00809-0700-4001
PV only
Percent of Range
PV, 2V, 3V, 4V
Process Variables
Device Status
Choosing burst mode options in HART 7
Message content options:
PV only
Percent of Range
PV, 2V, 3V, 4V
Process Variables and Status
Process Variables
Device Status
Choosing a HART 7 trigger mode
When in HART 7, you can select the following trigger modes:
Continuous (same as HART 5 burst mode)
Rising
Falling
Windowed
On Change
Note
Consult your host system manufacturer for burst mode requirements.
2.12.1
Configuring burst mode using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2.12.2
Configuring burst mode using AMS Device Manager
Procedure
1. Right click on the device and select Configure.
2. Select the HART tab.
3. Enter the configuration in Burst Mode Configuration fields.
Rosemount 3051P
Configuration
April 2020
2, 2, 5, 3