Mitsubishi Electric MELSEC iQ-R Series User Manual page 200

System recorder
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Event
Event type
code
2A032
Operation
2A040
Operation
2A050
Operation
2A051
Operation
2A052
Operation
2A053
Operation
2A054
Operation
2A055
Operation
5 TROUBLESHOOTING
198
5.7 Camera Recorder Module
Event
Overview
classificatio
n
Warning
Recording Files Saving Completion
Warning
Recording Files Saving Completion
Warning
Project Data Saving Failure
Warning
Project Data Saving Failure
Warning
Project Data Saving Failure
Warning
Project Data Saving Failure
Warning
Project Data Saving Failure
Warning
Project Data Saving Failure
Cause
• Saving the recording files has been completed.
• The sampled device and label data have exceeded
the size that can be stored in the recording buffer.
• Please set a sufficient size for the recording buffer
in the basic settings of the module parameter.
• Please set a shorter saving period before and after
the file saving trigger or saving period after the
recording startup trigger in the saving period
setting of the recording setting.
• Please reduce some device and label data to be
stored in the Device/Label sampling target setting
of the recording settings.
• Saving the recording files has been completed.
• Failed to save some video data.
Failed to save the project data because accessing
the SD memory card failed due to any one of the
following causes.
• The SD memory card is not inserted.
• The access status of the SD memory card is the
unmount state.
• The write-protect switch of the SD memory card is
enabled.
Failed to save the project data to the SD memory
card due to any one of the following causes.
• The free space in the SD memory card is
insufficient.
• An error of the SD memory card has been
detected.
Failed to save the project data because connecting
to the file server (the saving path set in the recording
setting) failed due to any one of the following causes.
• The saving path set in the saving path setting does
not exist.
• The user name/password set in the saving path
setting is incorrect.
• The host name/IP address set in the saving path
setting is incorrect.
• Any item in the DNS setting (the basic settings of
the module parameter) is incorrect.
• The file server is not connected to the network.
• The saving path set in the saving path setting or
files and folders under them are set Read-only or
Encrypt attributes.
Failed to save the project data to the file server (the
saving path set in the recording setting) due to any
one of the following causes.
• The free space in the file server is insufficient.
• The user set in the saving path setting does not
have write authority to the saving path.
• An error has been detected at the time of access to
the save destination folder due to network
disconnection.
• An error has been detected since several modules
and applications were accessing the saving
destination folder simultaneously.
• The saving path set in the saving path setting or
files and folders under them are set Read-only or
Encrypt attributes.
Since the CPU module is not supported by the
project data saving function, the project data was not
saved.
Since the project data in the CPU module was
changed while the project data was being saved, the
project data was not saved.

Advertisement